Critical · 9.9 Critical vulnerabilities CVE-2026-127057
Danfoss AK-SC 355 and AK-SM 800 Series Vulnerable to Default and Known Password Exploitation
Danfoss legacy AK-SC 355 and AK-SM 800 Series controllers ship with default credentials documented in the product manual, allowing unauthorized access. All versions are affected, and no fix is currently available.
By PatchBriefing ·
Produced automatically from official sources with the help of AI. How we work →
AI summary
A vulnerability has been disclosed affecting the Danfoss legacy AK-SC 355 and AK-SM 800 Series controllers. The issue, tracked as CVE-2026-127057, stems from the use of default or otherwise known credentials that are documented in the product manual, enabling unauthorized access to the devices. All versions of these products are affected, and no fix is currently available from the vendor.
What happened
Danfoss legacy AK-SC 355 and AK-SM 800 Series controllers were manufactured with default credentials that are documented in the product manual. If these credentials are not changed, or if other known passwords associated with the product are used, an attacker can gain unauthorized access to the device.
Technical cause
The vulnerability is classified under CWE-1392 (Use of Default Credentials). The devices rely on factory-set or otherwise known passwords for authentication, and these credentials are documented publicly in the product manual, making them readily discoverable by anyone with access to that documentation.
Why it matters
The vulnerability allows unauthorized access without requiring authentication or user interaction, and can be exploited over the network. Successful exploitation can impact confidentiality, integrity, and availability of the affected device, which is significant given that these controllers are used in building and refrigeration management systems.
Who is affected
Organizations operating Danfoss legacy AK-SC 355 or AK-SM 800 Series controllers are affected. All versions of these products are impacted, as the issue relates to credentials documented in the product manual rather than a specific software version.
Fixes and mitigation
No fix is currently available for this vulnerability. The fact package does not specify any vendor-provided patch or update. Organizations should independently verify whether default credentials have been changed on their devices and should not rely on an upcoming patch until one is confirmed available.
Recommended action
Operators of affected Danfoss controllers should immediately change any default or known credentials on these devices if not already done. Network access to these controllers should be restricted to trusted systems only, and exposure to untrusted networks, including the internet, should be avoided. Since no fix is currently available, these compensating controls are the primary means of reducing risk at this time.
PatchBriefing score
9.9 / 10 · Critical
Official CVSS: 9.9
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H
EPSS 0.0054 (39 percentile)
Why this score
The PatchBriefing score equals the official CVSS score; when this article covers several vulnerabilities, the highest one. Signals such as known exploitation and EPSS are listed separately and do not change the score.
Affected versions
Reported fixes
No fix is currently available for this vulnerability. The fact package does not specify any vendor-provided patch or update. Organizations should independently verify whether default credentials have been changed on their devices and should not rely on an upcoming patch until one is confirmed available.
How this was built
2 source records were collected, matched and used to prepare the report above.
-
NVD (NIST) database
-
CVE.org database
Revision history
- Published